YASKAWA Varispeed E7 Instruction Manual And Parameter Description page 105

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Tuning Constants: C
Acceleration/Deceleration: C1
Con-
stant
Number
Acceleration
C1-01
time 1
Deceleration
C1-02
time 1
Acceleration
C1-03
time 2
Deceleration
C1-04
time 2
Emergency stop
C1-09
time
Accel/decel time
C1-11
switching fre-
quency
S-Curve Acceleration/Deceleration: C2
Con-
stant
Number
S-curve character-
C2-01
istic time at accel-
eration start
S-curve character-
C2-02
istic time at accel-
eration end
-18
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Sets the acceleration time to accel-
erate from 0 Hz to the
maximum output frequency.
Sets the deceleration time to decel-
erate from the maximum output fre-
quency to 0 Hz.
Sets the acceleration time when the
multi-function input "accel/decel
time 1" is set to ON.
Sets the deceleration time when the
multi-function input "accel/decel
time 1" is set to ON.
Sets the deceleration time when the
multi-function input "Emergency
(fast) stop" is set to ON.
Sets the frequency for automatic
acceleration/deceleration switching.
If the output frequency is below the
set frequency: Accel/decel time 2
If the output freuquency is above
the set frequency: Accel/decel
time 1
The multi-function input "accel/
decel time 1" or "accel/decel time
2" has priority.
Name
Description
When the S-curve characteristic time is
set, the accel time will increase by only
half of the S-curve characteristic times
at start and end.
Run command
ON
Output frequency
C2-02
C2-01
= C2-01
T
+ C1-01 +
accel
2
The S-Curve characteristic time at start
and end of deceleration is fixed to 0.2
sec and can not be changed.
Setting
Factory
Range
Setting
0.0 to
10.0 s
6000.0
0.0 to
0.0 Hz
200.0
Setting
Factory
Range
Setting
0.20 s
OFF
0.00 to
2.50
Time
0.20 s
C2-02
2
Change
MEMO-
Access
during
BUS
Page
Opera-
Level
Register
tion
Yes
Q
200H
6-16
Yes
Q
201H
6-16
Yes
A
202H
6-16
Yes
A
203H
6-16
No
A
208H
6-15
No
A
20AH
6-17
Change
MEMO-
Access
during
BUS
Page
Level
Opera-
Register
tion
No
A
20BH
6-17
No
A
20CH
6-17
4-5
4-5