Detecting Motor Torque

If an excessive load is applied to the machinery (overtorque) or the load suddenly drops (undertorque), you
can output an alarm signal to one of the multi-function output terminal M1-M2 or M3-M4.
To use the overtorque/undertorque detection function, set B or 17 (overtorque/undertorque detection NO/NC)
in one of the constant H2-01 and H2-02 (multi-function output terminals M1-M2 and M3-M4 function selec-
tion).
The overtorque/undertorque detection level is the current level taking the inverter rated output current as
100%.
Related Constants
Con-
stant
Name
Number
L6-01
Torque detection selection 1
L6-02
Torque detection level 1
L6-03
Torque detection time 1
Multi-function Output (H2-01 and H2-02)
Set
Value
Overtorque/undertorque detection 1 NO
B
(NO contact: Overtorque detection and undertorque detection enabled when contact is ON)
Overtorque/undertorque detection 1 NC
17
(NC contact: Overtorque detection and undertorque detection enabled when contact is OFF)
L6-01 Set Value and Operator Display
The relationship between alarms displayed on the Digital Operator when overtorque or undertorque is
detected and the setting in L6-01 is shown in the following table.
Set
Value
0
Overtorque/undertorque detection disabled.
Overtorque detection only with speed agree; operation continues (warning is
1
output).
Overtorque detected continuously during operation; operation continues
2
(warning is output).
Overtorque detection only with speed agree; output is stopped upon detec-
3
tion.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
0: Overtorque/undertorque detection disabled.
1: Overtorque detection only with speed agreement; oper-
ation continues after overtorque (warning is output).
2: Overtorque detected continuously during operation;
operation continues (warning is output).
3: Overtorque detection only with speed agreement; out-
put is stopped upon detection.
4: Overtorque detected continuously during operation;
output is stopped upon detection.
5: Undertorque detection only with speed agreement;
operation continues (warning is output).
6: Undertorque detected continuously during operation;
operation continues (warning is output).
7: Undertorque detection only with speed agreement; out-
put is stopped upon detection.
8: Undertorque detected continuously during operation;
output is stopped upon detection.
Inverter rated current is set as 100%.
Set the overtorque/undertorque detection time.
Function
Function
Machine Protection
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 8
6
No
A
0 to 300
150%
No
A
0.0 to
10.0 s
No
A
10.0
Operator
Overtorque/ Under-
torque Detection 1
OL3 flashes
OL3 flashes
OL3 lights up
31
6-