YASKAWA Varispeed E7 Instruction Manual And Parameter Description page 108

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Reference Constants: d
Preset Reference: d1
Con-
Name
stant
Number
Frequency refer-
d1-01
ence 1
Frequency refer-
d1-02
ence 2
Frequency refer-
d1-03
ence 3
Frequency refer-
d1-04
ence 4
Jog frequency
d1-17
reference
Note: The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz).
Reference Limits: d2
Con-
Name
stant
Number
Frequency refer-
d2-01
ence upper limit
Frequency refer-
d2-02
ence lower limit
Master speed ref-
d2-03
erence lower limit
Note: The PI Sleep Function is also available and can be used without enabled PI controller. It can be used to let the
inverter switch off its output automatically when a minimum output frequency (set in b5-15) has been output for a
time longer than b5-16. Refer also to page 6-90.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Sets the frequency reference.
Sets the frequency reference when
multi-step speed command 1 is ON
for a multi-function input.
Sets the frequency reference when
multi-step speed command 2 is ON
for a multi-function input.
Sets the frequency reference when
multi-step speed commands 1 and 2
are ON for multi-function inputs.
Sets the frequency reference when
the jog frequency reference selec-
tion, FJOG command, or RJOG
command is ON.
Description
Sets the frequency reference upper
limit as a percentage of the max.
output frequency.
Sets the frequency reference lower
limit as a percentage of the maxi-
mum output frequency.
Sets the master speed reference
lower limit as a percentage of the
max. output frequency.
Change
Access
during
Setting
Factory
Range
Setting
Opera-
Level
tion
0.00 Hz
Yes
Q
0.00 Hz
Yes
Q
0.00 Hz
Yes
Q
0 to
FMAX
0.00 Hz
Yes
Q
6.00 Hz
Yes
Q
Change
Access
during
Setting
Factory
Range
Setting
Level
Opera-
tion
0.0 to
100.0%
No
A
110.0
0.0 to
0.0%
No
A
110.0
0.0 to
0.0%
No
A
110.0
User Constant Tables
MEMO-
BUS
Page
Register
280H
6-7
281H
6-7
282H
6-7
283H
6-7
6-7
292H
6-61
MEMO-
BUS
Page
Register
6-25
289H
6-55
6-25
28AH
6-55
6-25
293H
6-55
21
5-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cimr-e7c

Table of Contents