Stopping Methods

This section explains methods of stopping the Inverter.

Selecting the Stopping Method when a Stop Command is Input

There are four methods of stopping the Inverter when a stop command is input:
Deceleration to stop
Coast to stop
DC braking stop
Coast to stop with timer
Set constant b1-03 to select the Inverter stopping method.
Related Constants
Con-
stant
Name
Number
b1-03
Stopping method selection
Zero speed level (DC injection
b2-01
braking starting frequency)
b2-02
DC injection braking current
b2-04
DC injection braking time at stop
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Select stopping method when stop command is given.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than coast to stop, with-
out regenerative operation.)
3: Coast to stop with timer (Run commands are ignored
during deceleration time.)
Set the frequency at which the DC injection braking starts
in units of Hz when b1-03 is set to 0 (deceleration to stop).
DC injection braking starts from E1-09 when b2-01 <
E1-09.
Set the DC injection braking current as a percentage, tak-
ing the Inverter rated current as 100%.
Set the DC injection braking time at stop.
Use when stopping if rotations continue due to the
machines inertia.
Set to 0.00 to disable DC injection braking time at stop.

Stopping Methods

Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 3
0
No
Q
0.0 to
0.5 Hz
No
A
10.0
0 to
50%
No
A
100
0.00
to
0.50 s
No
A
10.00
11
6-