Wiring Control Circuit Terminals

Wire Sizes

For remote operation using analog signals, keep the control line length between the Analog Operator or oper-
ation signals and the Inverter to 50 m or less, and separate the lines from main power lines or other control cir-
cuits to reduce induction from peripheral devices.
When setting frequencies from an external frequency source (and not from a Digital Operator), used shielded
twisted-pair wires and ground the shield for the largest area of contact between shield and ground. See the fig-
ure below for details on the wiring.
2 kΩ
Terminal numbers and wire sizes are shown in
Terminals
FM, AC, AM, SC, SP,
SN, A1, A2, +V, S1, S2,
S3, S4, S5, S6, S7
MA, MB, MC, M1, M2,
M3, M4,
R+, R-, S+, S-, IG
E (G)
* 1. Use shielded twisted-pair cables to input an external frequency reference.
* 2. Refer to
Table 2.3 Lug Sizes
* 3. We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Analog input setting
adjustment
+V
2 kΩ
3
0 to 10V
A1
1
2
A2
4 to 20mA
P
P
AC
Fig 2.9
Table
Table 2.9 Terminal Numbers and Wire Sizes (Same for all Models)
Termi-
Tightening
nal
Torque
Screws
(N•m)
Phoenix
0.5 to 0.6
type
M3.5
0.8 to 1.0
for suitable lug sizes for the wires.
E(G)
Shield
terminal
Analog input power supply
+15V, 20mA
Analog input 1: Master frequency reference
0 to +10V (20 k )
Multi-functions analog input 2 [Default: Frequency bias,
4 to 20mA (250 )]
0V
2.9.
Recom-
Possible
mended
Wire Sizes
Wire Size
2
mm
(AWG)
2
mm
(AWG)
*3
Single wire
:
0.14 to 2.5
0.75
Stranded
(18)
wire:
0.14 to 1.5
(26 to 14)
*2
1.25
0.5 to 2
(12)
(20 to 14)

Wiring Control Circuit Terminals

Wire Type
*1
• Shielded, twisted-pair wire
• Shielded, polyethylene-cov-
ered, vinyl sheath cable
(KPEV-S by Hitachi Electrical
Wire or equivalent)
19
2-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cimr-e7c