Setting Precautions
If the motor capacity is small compared to the Inverter capacity or if the inverter is operated using the fac-
tory settings and the motor stalls, lower the set value of L3-02.
If using the motor in the constant output range, L3-02 will be automatically lowered to prevent stalling. It
will be reduced to a fixed value of 50 % of the inverter rated current.
Set the constants as a percentage taking the inverter rated current to be 100%.
Stall prevention level during
acceleration
Fig 6.19 Stall Prevention Level and Limit During Acceleration
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
E1-06
Base Frequency (FA)
Acceleration and Deceleration Characteristics
L3-02 (Stall Prevention Level during
Acceleration)
50 % of inverter rated current
Output frequency
19