Carrier Frequency and Inverter Overload Current Level
The inverter overload capability depends among other things on the carrier frequency setting. If the carrier
frequency setting is higher than the factory setting, the overload current capability must be reduced as shown
in the tables below.
-4
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Initial carrier
Inverter Type
frequency setting
20P4
6 (15 kHz)
20P7
6 (15 kHz)
21P5
6 (15 kHz)
22P2
6 (15 kHz)
23P7
6 (15 kHz)
25P5
6 (15 kHz)
27P5
6 (15 kHz)
2011
6 (15 kHz)
2015
6 (15 kHz)
2018
6 (15 kHz)
2022
6 (15 kHz)
2030
4 (10 kHz)
2037
3 (8 kHz)
2045
3 (8 kHz)
2055
3 (8 kHz)
2075
3 (5 kHz)
2090
3 (5 kHz)
2110
1 (2 kHz)
40P4
6 (15 kHz)
40P7
6 (15 kHz)
41P5
6 (15 kHz)
42P2
6 (15 kHz)
43P7
6 (15 kHz)
44P0
6 (15 kHz)
45P7
6 (15 kHz)
47P5
6 (15 kHz)
4011
6 (15 kHz)
4015
6 (15 kHz)
4018
6 (15 kHz)
4022
6 (15 kHz)
4030
4 (10 kHz)
4037
4 (10 kHz)
4045
4 (10 kHz)
4055
4 (10 kHz)
4075
3 (8 kHz)
4090
3 (8 kHz)
4110
3 (8 kHz)
4132
2 (5 kHz)
4160
2 (5 kHz)
4185
2 (5 kHz)
4220
1 (2.5 kHz)
4300
1 (2.5 kHz)
Maximum carrier
Current derating %
frequency setting
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
4 (10 kHz)
1 (2 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
6 (15 kHz)
80 %
6 (15 kHz)
80 %
6 (15 kHz)
80 %
6 (15 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
80 %
4 (10 kHz)
75 %
4 (10 kHz)