3.6 Control I/O Connections

3.6

Control I/O Connections

This section gives information about the settings for the listed control circuit I/O signals.
• MFDI (terminals S1 to S8)
• Pulse train output (terminal MP)
• MFAI (terminals A1 to A3)
• PTC input (terminal A3)
• MFAO (terminals FM, AM)
• MEMOBUS/Modbus communications (terminals D+, D-, AC)

Set Sinking Mode/Sourcing Mode

Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.
NOTICE: Damage to Equipment. Do not close the circuit between terminals SP-SN. If you close the circuits between terminals SC-
SP and terminals SC-SN at the same time, it will cause damage to the drive.
Mode
Sinking Mode (NPN)
Sourcing Mode
(PNP)

Pulse Train Output

You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
• Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Note:
Use the formula in
Figure 3.61
124
Internal Power Supply (Terminal SN-SP)
Load Impedance
R
(kΩ)
L
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more
to calculate the necessary load resistance (kΩ) to increase output voltage V
External 24 V power supply
Output Voltage
V
(V)
MP
5 V or more
8 V or more
10 V or more
(V).
MP
YASKAWA SIEPC71061737D GA800 Drive Technical Reference