Control Circuit Terminal Functions

The functions of the control circuit terminals are shown in
correct purposes.
No.
Signal Name
Type
S1
Forward run/stop command
S2
Reverse run/stop command
S3
External fault input
*
S4
Fault reset
Multi-step speed reference
*1
S5
1
Digital
(Master/auxiliary switch)
input
signals
Multi-step speed reference
S6
*1
2
S7
Jog frequency reference
SC
Digital input common
SN
Digital Input Neutral
SP
Digital Input Power Supply
+V
15 V power output
A1
Frequency reference
Analog
A2
Multi-function analog input
input
signals
AC
Analog reference common
Shield wire, optional ground
E(G)
line connection point
M1
Running signal
(1NO contact)
M2
M3
Se-
Zero speed
quence
output
M4
signals
MA
MB
Fault output signal
MC
Multi-function analog output
FM
(frequency output)
Analog
AC
Analog common
output
signals
Multi-function analog output
AM
(current monitor)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 2.11 Control Circuit Terminals with default settings
Forward run when ON; stopped when OFF.
Reverse run when ON; stopped when OFF.
*1
Fault when ON.
Reset when ON
Auxiliary frequency ref-
erence when ON.
Multi-step setting 2 when
ON.
*1
Jog frequency when ON.
+24VDC power supply for digital inputs
15 V power supply for analog references
0 to +10 V/100%
4 to 20 mA/100%
0 V to +10 V/100%
0 to 20 mA/100%
Operating when ON.
Zero level (b2-01) or
below when ON
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
0 to +10 V/100% fre-
quency
5 V/Inverter's rated cur-
rent
Wiring Control Circuit Terminals
Table
2.11. Use the appropriate terminals for the
Function
24 VDC, 8 mA
Functions are
Photocoupler isolation
selected by set-
ting H1-01 to
H1-05.
24 VDC, 250 mA max.
15 V
(Max. current: 20 mA)
0 to +10 V(20 kΩ)
Function is
4 to 20 mA(250Ω)
selected by set-
0 V to +10 V(20kΩ)
ting H3-09.
0 to 20 mA (250Ω)
Dry contacts
Contact capacity:
Multi-function
1 A max. at 250 VAC
contact outputs
1 A max. at 30 VDC
Multi-function
analog output 1
0 to +10 V max. ±5%
2 mA max.
Multi-function
analog output 2
Signal Level
*2
*3
21