Value
19
PI control disable (ON: PI control disabled)
Constants write enable (ON: All constants can be written-in. OFF: All constants are write pro-
1B
tected.)
1C
Trim control increase (ON: d4-02 frequency is added to analog frequency reference.)
1D
Trim control decrease (ON: d4-02 frequency is subtracted from analog frequency reference.)
1E
Analog frequency reference sample/hold
External fault
20 to 2F
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
30
PI control integral reset (reset when reset command is input or when stopped during PI control)
31
PI control integral hold (ON: Hold)
34
PI soft starter disable (ON: disabled)
35
PI input characteristics switch
36
Operation Source Option/Inverter selection 2 (ON: inverter settings)
60
Motor preheat command (ON: Performs motor preheat)
61
External search command 1 (ON: Speed search from maximum output frequency)
62
External search command 2 (ON: Speed search from set frequency)
64
External speed search command 3
65
KEB (deceleration at momentary power loss) command (NC contact)
66
KEB (deceleration at momentary power loss) command (NO contact)
67
Communications test mode
68
High-slip braking (HSB)
69
Jog Frequency 2
6A
Drive enable (NC, ON: Drive enabled, OFF: Drive disabled
6B
Operation Source Communication/Inverter selection (ON: RS-422/485 port)
6C
Operation Source Communication/Inverter selection 2 (ON: inverter settings)
6D
AUTO mode selection (ON: AUTO mode active)
6E
HAND mode selection (ON: HAND mode active)
6F
Maintenance Mode
70
Bypass Drive Enable
Multi-function Contact Outputs: H2
Con-
Name
stant
Number
Terminal M1-M2
Multi-function contact
H2-01
function selection
output 1
Terminal M3-M4
Multi-function contact
H2-02
function selection
output 2
Multi-function Contact Output Functions
Setting
Value
0
During run (ON: run command is ON or voltage is being output)
1
Zero-speed
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Function
Setting
Description
Range
0 to 38
0 to 38
Function
User Constant Tables
Change
MEMO-
Access
during
Factory
BUS
Setting
Level
Opera-
Register
tion
0
No
A
40BH
1
No
A
40CH
Page
6-86
6-109
6-58
6-58
6-59
6-62
6-86
6-86
6-86
6-86
6-60
6-14
6-40
6-40
6-39
6-81
6-101
6-8
6-53
6-60
6-60
6-61
6-61
6-53
Page
Page
6-63
6-64
27
5-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cimr-e7c

Table of Contents