Raising And Lowering Frequency References Using Contact Signals (Up/Down) - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Raising and Lowering Frequency References Using Contact Signals
(UP/DOWN)
The UP and DOWN commands raise and lower Inverter frequency references by turning ON and OFF a
multi-function contact input terminal S3 to S7.
To use this function, set two of the constants H1-01 to H1-05 (multi-function contact input terminal S3 to S7
function selection) to 10 (UP command) and 11 (DOWN command). Be sure to allocate two terminals so that
the UP and DOWN commands are used as a pair. Otherwise an OPE03 alarm will be displayed.
The table below shows the possible combinations of the UP and DOWN command and the corresponding
operation.
Operation
Up command
Down command
The change of the output frequency depends on the acceleration and deceleration times. Be sure to set b1-02
(Run command selection) to 1 (Control circuit terminal).
Related Constants
Con-
stant
Name
Number
d2-01
Frequency reference upper limit
d2-02
Frequency reference lower limit
Master speed reference lower
d2-03
limit
Precautions
Setting Precautions
If multi-function input terminals S3 to S7 are set as follows, operation error OPE03 (Invalid multi-function
input selection) will occur:
Only either the UP command or DOWN command has been set.
UP/DOWN commands and Acceleration/Deceleration Ramp Hold have been allocated at the same time.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Acceleration Deceleration
ON
OFF
OFF
ON
Description
Sets the frequency reference upper limit as a percent, tak-
ing the maximum output frequency to be 100%.
Sets the frequency reference lower limit as a percentage of
the maximum output frequency.
Sets the master speed frequency reference lower limit as a
percent, taking the maximum output frequency to be
100%.
Input Terminal Functions
Hold
Hold
ON
OFF
ON
OFF
Change
Setting
Factory
during
Range
Setting
Opera-
0.0 to
100.0%
110.0
0.0 to
0.0%
110.0
0.0 to
0.0%
110.0
Access
Level
tion
No
A
No
A
No
A
55
6-