Continuing Operation At Constant Speed When Frequency Reference Is Lost - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Continuing Operation at Constant Speed When Frequency
Reference Is Lost
The frequency reference loss detection function can be used to continue operation at reduced speed using the
set value in parameter L4-06 as frequency reference value. When using an analog input as frequency reference
source, a frequency reference loss is detected, when the reference value drops over 90 % in 400 ms or less.
When an error signal during frequency reference loss shall be output externally, set H2-01 or H2-02
(multi-function contact output terminal M1-M2 and M3-M4 function selection) to C (frequency reference
lost).
Related Constants
Con-
stant
Number
Operation when frequency refer-
L4-05
ence is missing
Output frequency adjustment after
L4-06
freq. reference loss
-44
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
0: Stop
1: Operation (L4-06*fref@loss) inverter runs with
reduced speed.
Frequency reference loss means that the frequency refer-
ence drops over 90% in 400 ms.
If L4-05 is set to 1 and the reference is lost, inverter will
run at:
fout = L4-06*fref@loss
Setting
Description
Range
0 or 1
100%
Change
Factory
during
Access
Setting
Opera-
Level
tion
1
No
A
0 to
80%
No
A