Motor Setup: E2
Con-
stant
Number
Motor rated cur-
E2-01
rent
Motor no-load
E2-03
current
Motor line-to-line
E2-05
resistance
* 1. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V class inverter of 0.4 kW is given.
* 2. The factory setting depends upon the Inverter capacity. The value for a 200 V class inverter of 0.4 kW is given.
* 3. The setting range depends on the inverter capacity. The values for a 200 V class inverter of 0.4 kW are given.
-24
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Sets the motor rated current.
This set value will become the ref-
erence value for motor protection
and torque limits.
This constant is an input data for
autotuning.
Sets the motor no-load current.
This constant is automatically set
during autotuning.
Sets the motor phase-to-phase resis-
tance in Ω units.
This constant is automatically set
during autotuning.
Change
Access
during
Setting
Factory
Range
Setting
Level
Opera-
tion
0.32 to
1.90 A
No
Q
6.40
*2
*1
0.00 to
*2
No
A
1, 2
*3
1.89
0.000
9.842 Ω
to
No
A
*2
65.000
MEMO-
BUS
Page
Register
6-33
30EH
6-94
310H
312H
6-94