Switching Operation Source to Communication Option Card

The source of frequency reference and RUN command can be switched between a Communication option
card and the sources selected in b1-01 and b1-02. Set one of the constants H1-01 to H1-05 (multi-function
contact inputs S3 to S7 function selection) to 2 or 36 to enable operation source switchover.
If a RUN command is active, the switchover will not be accepted.
Setting Precautions
To use the operation source switching function make the following settings:
Set b1-01 (frequency reference source) to a value different from 3 (option card).
Set b1-02 (RUN command source) to a value different from 3 (option card).
Set one of the constants H1-01 to H1-05 to 2 or 36.
Setting for one of
H1-01 to H1-05
Terminal Status

Switching Operation Source to MEMOBUS communication

The frequency reference and RUN command source can be switched between the MEMOBUS-communica-
tion via RS-422/485 and the inverter settings in b1-01 and b1-02. Therefore set one of the parameters H1-01
to H1-05 (multi-function digital inputs S3 to S7) to 6B or 6C.
If a RUN command is active the switchover will not be accepted.
Setting precautions
To use the operation source switching function make the following settings:
Set b1-01 (Frequency reference source) to a value different from 3 (option card)
Set b1-02 (RUN command source) to a value different from 3 (option card)
Set one of the constants H1-01 to H1-05 to 6B or 6C
-60
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Terminal
Status
Inverter
OFF
(Frequency reference and Run command source are set in b1-01 and b1-02)
2
Communication option card
ON
(Frequency reference and run command are input from communications option
card)
Communication option card
OFF
(Frequency reference and run command are input from communications option
card)
36
Inverter
ON
(Frequency reference and Run command source are set in b1-01 and b1-02)
Inverter
OFF
(Frequency reference and RUN command source are set in b1-01 and b1-02.)
Communications Option Card
ON
(Frequency reference and run command are enabled from communications Option Card.)
Frequency Reference and Run Command Source
Frequency Reference and Run Command Selection