Adjusting Frequency References

This section explains methods of adjusting frequency references.

Adjusting Analog Frequency References

Gain and bias are among the constants used to adjust analog inputs.
Related Constants
Con-
stant
Number
Frequency reference terminal A1
H3-02
input gain
Frequency reference terminal A1
H3-03
input bias
Multi-function analog A2 signal
H3-08
level selection
Multi-function analog A2 func-
H3-09
tion selection
Multi-function analog A2 input
H3-10
gain
Multi-function analog A2 input
H3-11
bias
Analog input filter time constant
H3-12
H3-13
Terminal A1/A2 switching
Adjusting Analog Frequency Reference Using Constants
The frequency reference can be input from the control circuit terminals using analog voltage and current sig-
nals.
If using terminal A1 as an input terminal for the frequency reference value, perform adjustments using con-
stants H3-01 to H3-03. If using multi-function analog input terminal A2 as a frequency reference terminal,
perform adjustments using H3-08 to H3-11. Set the analog input signal level using the constants H3-01 or
H3-08. Refer the following figures for setting the input gain and bias.
Frequency reference
-22
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Sets the frequency as a percentage of the maximum output
frequency, when 10V is input.
Sets the frequency as a percentage of the maximum output
frequency, when 0V is input.
0: 0 to +10V (11 bit)
2: 4 to 20 mA (9-bit input)
3: 0 to 20 mA (9-bit input)
Switch current and voltage input using the switch S1 on
the control terminal board.
Selects the multi-function analog input function for termi-
nal A2.
Sets the input levelwhen terminal A2 input is 10V (20mA)
according to the 100% value of the function set in constant
H3-09.
Sets the input level when terminal A2 input is 0V (4mA)
according to the 100% value of the function set in constant
H3-09.
Sets primary delay filter time constant for the two analog
input terminals (A1 and A2). Effective for noise control
etc.
0: Use terminal A1 analog input as main frequency refer-
ence.
1: Use terminal A2 analog input as main frequency refer-
ence.
Effective when H3-09 is set to 2.
Terminal
input voltage
Terminal A1 input
Fig 6.21 Terminals A1 and A2 Inputs
Description
Frequency reference
A1
0V (4 mA/0 mA)
Terminal A2 input
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.0 to
100.0%
Yes
A
1000.0
-100.0
to
0.0%
Yes
A
+100.0
0, 2, 3
2
No
A
0 to 16
0
No
A
0.0 to
100.0%
Yes
A
1000.0
-100.0
to
0.0%
Yes
A
+100.0
0.00 to
0.00 s
No
A
2.00
0 or 1
0
No
A
Terminal A2 input
voltage (current)