Application Precautions
Jog frequencies using FJOG and RJOG commands have the priority over other frequency references.
When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).

Stopping the Inverter on External Device Errors (External Error Function)

The external error function activates the error contact output and stops the Inverter operation. Using this func-
tion the inverter operation can be stopped on peripheral devices break down or other errors. The digital opera-
tor will display EFx (External error [input terminal Sx]). The x in EFx shows the number of the terminal at
which the external error signal is input. For example, if an external error signal is input to terminal S3, EF3
will be displayed.
To use the external error function, set one of the values 20 to 2F in one of the constants H1-01 to H1-05
(multi-function contact input terminal S3 to S7 function selection).
Select the value to be set in H1-01 to H1-05 from a combination of any of the following three conditions.
Signal input level from peripheral devices
External error detection method
Operation during external error detection
The following table shows the relationship between the combinations of conditions and the set value in
H1-
.
Set
Value
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
Note: 1. Sets the input level at which errors are detected. (NO contact: External error when ON; NC contact: External error when OFF).
2. Set the detection method to detect errors using either constant detection or detection during operation.
Constant detection: Detects while power is supplied to the Inverter.
Detection during operation: Detects only during Inverter operation.
-62
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Input Level
Error Detection Method
(See Note 1.)
NO Con-
NC Con-
Constant
tact
tact
Detection
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(See Note 2.)
Detection
Deceler-
During
ate to Stop
Operation
(Error)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Operation During Error Detection
Emer-
Coast to
gency
Stop
Stop
(Error)
(Error)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Continue
Operation
(Warning)
Yes
Yes
Yes
Yes