Square Root Feedback Operation
If parameter b5-28 is set to 1 the feedback value is converted into a value that equals the square root of the
actual feedback. This can be used to control the flow rate when a pressure sensor is used to generate a feed-
back value. With parameter b5-29 the square root can be multiplied with a factor. Following formula applies:
So linear connection between the PI target value and the feedback can be realized.
With parameter b5-30 also the feedback monitor can be switched to show a square root value of the actual
feedback.
Multifunction Digital Input Settings: H1-01 to H1-05 (Terminal S3 bis S7)
PI Control Disable: "19"
When a multifunction input is set for this function it can be used to disable the PI function by switching the
input to ON.
The PI target value becomes the frequency reference value.
PI Control Integral Reset: "30"
Using this function the integral share value of the PI control can be reset by setting a multifunction input to
ON.
PI Control Integral Hold: "31"
Using this function the integral share value of the PI control can be hold by setting a multifunction input to
ON. The value will be hold as long as the input is ON.
PI Softstarter: "34"
Using this function the PI target value can be raised or lowered slowly using an accel./decel. ramp
function. The accel./decel. time can be set in constant b5-17. The function is active when the multi-
function input with this function is ON.
PI Input Characteristic Switch: "35"
Using this function the PI input characteristic can be inverted by setting a multifunction input to ON.
-92
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
flow rate = gain (b5-29) x √pressure (head)