Constant
Name
Number
Multi-function
analog input ter-
H3-09
minal A2 func-
tion selection
Gain (terminal
H3-10
A2)
Bias (terminal
H3-11
A2)
Analog input filter
H3-12
time constant
Terminal A1/A2
H3-13
switching
H3-09 Settings
Setting
Value
0
Frequency bias
Auxiliary frequency reference (is used as
2
frequency reference 2)
B
PI feedback
D
Frequency Bias 2
E
Motor temperature input
16
PI differential mode
1F
Analog input not used.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Selects the multi-function analog
input function for terminal A2.
Refer to the table on the next
page.
Sets the input level when terminal
A2 input is 10 V (20 mA) accord-
ing to the 100% value of the func-
tion set in constant H3-09.
Sets the input level when terminal
A2 is 0 V (4 mA/0 mA) according
to the 100% value of the function
set in constant H3-09.
Sets primary delay filter time con-
stant for the two analog input ter-
minals (A1 and A2).
Effective for noise supression etc.
0: Use terminal A1 analog input
as main frequency reference.
1: Use terminal A2 analog input
as main frequency reference.
Effective when H3-09 is set to 2.
Function
Maximum output frequency
Maximum output frequency
Maximum output frequency
Maximum output frequency
Maximum output frequency
Change
Access
during
Setting
Factory
Range
Setting
Level
Opera-
tion
0 to 16
0
No
A
0.0 to
100.0%
Yes
A
1000.0
-100.0
to
0.0%
Yes
A
+100.0
0.00 to
0.00
No
A
2.00
s
0 or 1
0
No
A
Contents (100%)
User Constant Tables
MEMO-
BUS
Page
Register
418H
6-22
419H
6-22
41AH
6-22
41BH
6-22
41CH
Page
6-22
6-5
6-22
6-36
29