Run Command; Selecting The Run Command Source - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Run Command

This section explains input methods for the run command.

Selecting the Run Command Source

Set constant b1-02 to select the source for the run command.
Related Constants
Con-
stant
Name
Number
b1-02
Operation method selection
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP, and
FWD/REV). For details on the Digital Operator, refer to
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.
Performing Operations Using a 2-wire Control
The factory setting is set to a 2-wire control. When control circuit terminal S1 is set to ON, forward operation
will be performed, and when S1 is turned OFF, the Inverter will stop. In the same way, when control circuit
terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Inverter will
stop.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Set the run command source.
0: Digital operator
1: Control circuit terminal (digital multifunction inputs)
2: MEMOBUS communications
3: Option Card
Forward/Stop
Reverse/Stop
SN
Fig 6.8 2-Wire Control Wiring Example with Positive Logic
Setting
Range
0 to 3
Chapter 3 Digital Operator and
Inverter
Digital input neutral

Run Command

Change
Factory
during
Access
Setting
Opera-
Level
tion
1
No
Q
Modes.
9