Autotuning automatically measures and sets the motor line-to-line resistance of the motor and motor cable to
compensate the voltage drop and thereby to achieve the best performance.
Example of Operation
Set the motor rated output power (in kW) and the motor rated current, specified on the motor nameplate and
then press the RUN key. The motor is automatically run and the line-to-line resistance is measured.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET keys to
change the setting. The user constant will be written and the display will be returned to monitor display when
the DATA/ENTER key is pressed.
The following example shows the autotuning procedure.
Autotuning
If a fault occurs during autotuning, refer to
IMPORTANT
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Autotuning Monitor Display
Motor output power
Motor rated current
Autotuning start*
Fig 3.8 Operation in Autotuning Mode
Chapter 7
Setting Display
Motor output power
Motor rated current
Stop command input
Autotuning
Autotuning completed