Individual Functions
Using MEMOBUS Communications
You can perform serial communications with Programmable Logic Controls (PLCs) or similar devices using
the MEMOBUS protocol.
MEMOBUS Communications Configuration
MEMOBUS communications are configured using 1 master (PLC) and a maximum of 31 slaves. Serial com-
munications between master and slave are normally started by the master and the slaves respond.
The master performs serial communications with only one slave at a time. Consequently, you must set the
address of each slave before, so that the master can perform serial communications using that address. A slave
that receives a command from the master performs the specified function and sends a response to the master.
Communications Specifications
The MEMOBUS communications specifications are shown in the following table.
Interface
Communications Cycle
Communications Parameters
Communications Protocol
Number of Connectable Units
-68
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
PLC
Fig 6.43 Example of Connections between PLC and Inverter
Item
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate:
Data length:
Parity:
Stop bits:
MEMOBUS
31 units max.
Inverter
Inverter
Specifications
Select from 1,200, 2,400, 4,800, 9,600 and 19,200 bps.
8 bits fixed
Select from even, odd, or none.
1 bit selected
Inverter