Option Constants: F - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Option Constants: F

Communications Option Cards: F6
Con-
Name
stant
Number
Operation selec-
F6-01
tion after commu-
nications error
Input level of
external error
F6-02
from Communica-
tions Option Card
Stopping method
for external error
F6-03
from Communica-
tions Option Card
Current monitor
F6-05
unit selection
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Set the stopping method for com-
munications errors.
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0: Always detect
1: Detect during operation
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
Sets the unit of current monitor
0: Ampere
1: 100%/8192
User Constant Tables
Change
Access
during
Setting
Factory
Range
Setting
Opera-
Level
tion
0 to 3
1
No
A
0 or 1
0
No
A
0 to 3
1
No
A
0 or 1
1
No
A
MEMO-
BUS
Page
Register
3A2H
3A3H
3A4H
3A6H
25
5-