Machine Protection; Preventing Motor Stalling During Operation - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Machine Protection

Preventing Motor Stalling During Operation

Stall prevention during operation prevents the motor from stalling by automatically lowering the Inverter's
output frequency when a transient overload occurs while the motor is operating at a constant speed.
If the Inverter output current continues to exceed the setting in constant L3-06 for 100 ms or longer, the motor
speed is reduced. Set whether to enable or disable the stall prevention using constant L3-05. Set the according
deceleration times using C1-02 (Deceleration time 1) or C1-04 (Deceleration Time 2).
If the Inverter output current reaches the set value in L3-06 – 2%, the motor will accelerate again to the set fre-
quency.
Related Constants
Con-
stant
Number
Stall prevention selection during
L3-05
running function selection
Stall prevention level during run-
L3-06
ning
-30
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
0: Disabled (Operates according to the setting. Motor
may stall when the load is too large.)
1: Enabled--Deceleration time 1 (Deceleration time set in
C1-02 is used.)
2: Enabled--Deceleration time 2 (Deceleration time set in
C1-04 is used.)
Enabled when L3-05 is set to 1 or 2. Set as a percentage,
taking Inverter rated current to be 100%.
Normally, there is no need to change this setting.
Lower the set value if the motor stalls at the factory set-
ting.
Setting
Description
Range
0 to 2
30 to 200
Change
Factory
during
Access
Setting
Opera-
Level
tion
1
No
A
120%
No
A