Setting for one of
Terminal
H1-01 to H1-05
Status
6B
6C

AUTO/HAND Mode Switching by Digital Input

The settings 6D and 6E for H1-01 to H1-05 allow to switch between HAND and AUTO mode by digital input.
Both signals cannot both be programmed simultaneously.
If the Auto Mode Selection is programmed into a digital input, the Auto mode will be selected whenever that
input is closed. The status of the Auto Mode Selection digital input will override any digital operator selec-
tions.
If the Hand Mode Selection is programmed into a digital input, the Hand mode will be selected whenever that
input is closed. The status of the Hand Mode Selection digital input will override any digital operator selec-
tions.
Using either the Auto Mode Selection or the Hand Mode Selection can only be done when the Drive is
stopped.
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG function operates the inverter at the jog frequency. It can be activated by using the terminal
ON/OFF operation. When using the FJOG/RJOG commands, there is no need to input the RUN command.
To use this function, set one of the constants H1-01 to H1-05 (multi-function contact input terminal S3 to S7
function selection) to 12 (FJOG command) or 13 (RJOG command).
Related Constants
Con-
stant
Name
Number
d1-17
Jog frequency reference
Multi-Function Contact Inputs (H1-01 to H1-05)
Set
Value
12
FJOG command (ON: Forward run at jog frequency d1-17)
13
RJOG command (ON: Reverse run at jog frequency d1-17)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Frequency Reference and Run Command Source
Inverter
OFF
(Frequency reference and Run command source are set in b1-01 and b1-02)
MEMOBUS communication
ON
(Frequency reference and run command are input via RS-422/485)
MEMOBUS communication
OFF
(Frequency reference and run command are input via RS-422/485)
Inverter
ON
(Frequency reference and Run command source are set in b1-01 and b1-02)
Description
Sets the frequency reference when the jog frequency refer-
ence selection, FJOG command, or RJOG command is
ON.
Function
Input Terminal Functions
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to
6.00 Hz
Yes
Q
120.00
61
6-