Input Terminal Functions
Temporarily Switching Operation between Digital Operator
and Control Circuit Terminals
You can switch the Inverter run command inputs and frequency reference inputs between local (i.e., Digital
Operator) and remote (input method set in b1-01 and b1-02).
If any input from H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function selection) has been
set to 1 (local/remote selection), this input can be used to switch over between local and remote.
To set the frequency reference source and RUN command source to control circuit terminals, set b1-01 and
b1-02 to 1.
Related Constants
Con-
stant
Name
Number
b1-01
Reference selection
b1-02
RUN command source selection
You can also perform local/remote switching using the LOCAL/REMOTE key on the Digital Operator. When
the local/remote function has been set for one external terminal, the LOCAL/REMOTE key function on the
Digital Operator will be disabled.
INFO
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Sets the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
Sets the run command input method
0: Digital Operator
1: Control circuit terminal (digital multifunction inputs)
2: MEMOBUS communications
3: Option Card
Input Terminal Functions
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 3
1
No
Q
0 to 3
1
No
Q
51
6-