YASKAWA Varispeed E7 Instruction Manual And Parameter Description page 137

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Con-
stant
Number
o2-04
b8-04
C6-02
E2-01
E2-03
E2-05
L2-02
L2-03
L2-04
L8-02
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V class
Inverters with outputs of 0.4 to 11 kW.
* If C6-02 is set to 0, 1, or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz,
4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the
Inverter rated current will need to be reduced.
-50
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Unit
Inverter Capacity
kW
kVA selection
Energy-saving coeffi-
cient
Carrier frequency selec-
*
tion
Motor rated current
A
Motor no-load current
A
Motor line-to-line resis-
tance
Momentary power loss
s
ridethru time
Min. baseblock (BB)
s
time
Voltage recovery time
s
°C
Overheat pre-alarm level
Factory Setting
160
185
220
300
34
35
36
37
30.13
30.57
27.13
21.76
2
2
1
1
270.0
310.0
370.0
500.0
70.0
81.0
96.0
130.0
0.029
0.025
0.020
0.014
2.0
2.0
2.0
2.0
1.8
1.9
2.0
2.1
1.0
1.0
1.0
1.0
108
95
100
108