Using the Timer Function

The multi-function digital input terminals S3 to S7 can be used as timer function input terminals, and
multi-function output terminals M1-M2 and M3-M4 can be used as timer function output terminals. By setting
the delay time, you can prevent chattering of the sensors and switches.
Set one of the constants H1-01 to H1-05 (multi-function contact input terminal S3 to S7) to 18 (timer func-
tion input).
Set H2-01 or H2-02 (multi-function output terminals M1-M2 and M3-M4 function selection) to 12 (timer
function output).
Related Constants
Con-
stant
Number
b4-01
Timer function ON-delay time
b4-02
Timer function OFF-delay time
Setting Example
When the timer function input ON time is longer than the value set in b4-01, the timer output function is
turned ON. When the timer function input OFF time is longer than the value set in b4-02, the timer output
function is turned OFF. An example of timer function operation is given in the following diagram.
Timer function input
Timer function output
-82
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Set the timer function output ON delay time (dead time)
for the timer function input in 1-second units. Enabled
when a timer function is set in H1-
Set the timer function output OFF delay time (dead time)
for the timer function input in 1-second units. Enabled
when the timer function is set in H1-
Fig 6.47 Timer Function Operation Example
Setting
Description
Range
0.0 to
300.0
and H2-
.
0.0 to
300.0
and H2-
.
Change
Factory
during
Access
Setting
Opera-
Level
tion
0.0 s
No
A
0.0 s
No
A