YASKAWA Varispeed E7 Instruction Manual And Parameter Description page 127

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Con-
stant
Number
3rd Monitor
o1-08
Selection
* 1. Parameter is only effective if HOA operator with LCD (JVOP-162) is used.
Multi-function Selections: o2
Con-
stant
Number
LOCAL/
o2-01
REMOTE key
enable/disable
STOP key during
o2-02
control circuit ter-
minal operation
User constant ini-
o2-03
tial value
o2-04 kVA selection
Frequency refer-
o2-05
ence setting
method selection
Operation selec-
tion when digital
o2-06
operator is discon-
nected
-40
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Description
Selects the monitor that is displayed
and locked in the third line of the
*1
operator display.
Name
Description
Sets the Digital Operator Local/
Remote key
0: Disabled
1: Enabled (Switches between the
Digital Operator and the
constant settings b1-01, b1-02.)
Sets the Stop key in the run mode.
0: Disabled (When the run
command is issued from an
external terminal, the Stop key is
disabled.)
1: Enabled (Effective even during
run.)
Clears or stores user initial values.
0: Stores/not set
1: Begins storing (Records the set
constants as user initial values.)
2: All clear (Clears all recorded
user initial values)
When the set constants are recorded
as user initial values, 1110 will be
set in A1-03.
Do not set unless using a control
board from an Inverter with a dif-
ferent capacity. (Refer to page 5-48
for the setting values).
When the frequency reference is set
on the Digital Operator frequency
reference monitor, sets whether the
Enter key is necessary or not.
0: Enter key needed
1: Enter key not needed
When set to 1, the Inverter accepts
the frequency reference without
Enter key operation.
Sets the operation when the Digital
Operator is disconnected.
0: Disabled (Operation continues
even if the Digital Operator is
disconnected.)
1: Enabled (OPR is detected at
Digital Operator disconnection.
Inverter output is switched off,
and fault contact is operated.)
Change
Access
during
Setting
Factory
Range
Setting
Level
Opera-
tion
1 to 53
3
No
A
Change
Access
during
Setting
Factory
Range
Setting
Opera-
Level
tion
0 or 1
1
No
A
0 or 1
1
No
A
0 to 2
0
No
A
0 to FF
No
A
0
0 or 1
0
No
A
0 or 1
0
No
A
MEMO-
BUS
Page
Register
519H
MEMO-
BUS
Page
Register
505H
6-102
506H
6-102
507H
6-102
508H
-
509H
6-102
50AH
6-102