Table 88: Calculating Power Budget for a MX480 AC Chassis
Power Supply
MX480 AC Normal-capacity (low-line)
MX480 AC Normal-capacity (high-line)
MX480 AC High-capacity (low-line)
MX480 AC High-capacity (high-line)
1
For this configuration, output power excluding the cooling system is 1360 W.
Table 89: Calculating Power Budget for a MX480 DC Chassis
Power Supply
MX480 DC Normal-capacity
MX480 DC High-capacity (DIP=0)
NOTE:
The DIP switch position is expected input
current; the correct feeds must be present to obtain
the desired output power.
MX480 DC High-capacity (DIP=1)
NOTE:
The DIP switch position is expected input
current; the correct feeds must be present to obtain
the desired output power.
1
For this configuration, output power excluding the cooling system is 1010 W.
2
For this configuration, output power excluding the cooling system is 770 W.
3. Calculate input power. In this step, the input power requirements for the example configuration are
calculated. To do this, divide the total output requirement by the efficiency of the power supply as
shown in
Table 90 on page
and
for more information about the MX480 power supply electrical
Maximum System Output
Power
3081 W
3200 W
3501 W
4100 W
Maximum System
Output Power
3200 W
4800 W
5200 W
204.
"DC Power Supply Electrical Specifications for
Zone 0 Unused
1
Power
2190 W
3790 W
4190W
1
Unused Power
2071 W
2190 W
2491 W
3090 W
Zone 1 Unused
2
Power
2430 W
4030 W
4430W