Table 82: Router Environmental Specifications (continued)
Description
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the router only in restricted areas, such as dedicated equipment rooms and
equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.
SEE ALSO
Tools and Parts Required to Maintain the MX480 Router
In Case of an Electrical Accident
Value
Normal operation ensured in relative humidity range of 5% to
90%, noncondensing
Normal operation ensured in temperature range of 32°F (0°C)
to 104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 11,322 BTU/hour (3,318 W)
DC power: 9,632 BTU/hour (2,823 W)
NOTE:
These specifications are estimates and subject to
change.