B.6 F: Option Settings
B.6 F: Option Settings
F parameters program the drive for PG feedback from the motor and to function with option cards.
u

F1: PG Speed Control Card (PG-B3, PG-X3, PG-RT3, PG-F3)

Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 include "PG 1" in the parameter name and are used
to set up a PG option card plugged into option port CN5-C of the drive.
Parameters F1-31 through F1-37 include "PG 2" in the parameter name and are used to set up a PG option card plugged into
option port CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into port CN5-C and CN5-B.
No.
(Addr.
Name
Hex)
F1-01
PG 1 Pulses Per
(0380)
Revolution
F1-02
Operation Selection at
(0381)
PG Open Circuit (PGo)
F1-03
Operation Selection at
(0382)
Overspeed (oS)
F1-04
Operation Selection at
(0383)
Deviation
F1-05
PG 1 Rotation Selection
(0384)
F1-06
PG 1 Division Rate for
(0385)
PG Pulse Monitor
F1-08
Overspeed Detection
(0387)
Level
F1-09
Overspeed Detection
(0388)
Delay Time
Excessive Speed
F1-10
Deviation Detection
(0389)
Level
Excessive Speed
F1-11
Deviation Detection
(038A)
Delay Time
278
LCD Display
Sets the number of PG (pulse generator or encoder) pulses. Sets
the number of pulses per motor revolution.
PG1 Pulses/Rev
Note:
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
PG Fdbk Loss Sel
1: Coast to stop.
0: Ramp to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
1: Coast to Stop
C1-09.
2: Fast-Stop
3: Alarm only.
3: Alarm Only
4: No alarm display
4: Not Detect
Note:
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
PG Overspeed Sel
2: Fast Stop. Decelerate to stop using the deceleration time in
0: Ramp to Stop
C1-09.
1: Coast to Stop
3: Alarm only.
2: Fast-Stop
3: Alarm Only
Note:
0: Ramp to stop. Decelerate to stop using the deceleration time
PG Deviation Sel
in C1-02.
0: Ramp to Stop
1: Coast to stop.
1: Coast to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
2: Fast-Stop
C1-09.
3: Alarm Only
3: Alarm only.
PG1 Rotation Sel
0: Pulse A leads
0: Fwd = C.C.W
1: Pulse B leads
1: Fwd = C.W.
Sets the division ratio for the pulse monitor used of the PG
option card installed to port CN5-C.
When setting for a three-digit number "xyz", the division ratio
becomes = [(1 + x) / yz].
PG1 Output Ratio
If only using the A pulse for one-track input, the input ratio will
be 1:1 regardless of F1-06 setting.
Note:
Sets the overspeed detection level as a percentage of the
PG Overspd Level
maximum output frequency.
Sets the time in seconds for an overspeed situation to trigger a
fault (oS).
PG Overspd Time
Sets the speed deviation detection level as a percentage of the
PG Deviate Level
maximum output frequency.
Sets the time in seconds for a speed deviation situation to trigger
PG Deviate Time
a fault (dEv).
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
Setting range is 0 to 15000 ppr when A1-02 = 7
(CLV/PM control mode).
Depending on motor speed and load conditions,
an error such as ov or oC may occur.
In AOLV/PM, the motor will coast to a stop
(F1-03 = 1). The setting for F1-03 cannot be
changed to 0, 2, or 3.
Values 033 to 101 are not available.
Values
Page
Default: 1024 ppr
Min.: 1
Max.: 60000
Default: 1
Range: 0 to 4
Default: 1
Range: 0 to 3
Default: 3
Range: 0 to 3
<1>
Default:
Range: 0, 1
Default: 001
Min.: 001
Max.: 132
Default: 115%
Min.: 0
Max.: 120
<1>
Default:
Min.: 0.0 s
Max.: 2.0 s
Default: 10%
Min.: 0
Max.: 50
Default: 0.5 s
Min.: 0.0
Max.: 10.0