4.6 Basic Drive Setup Adjustments
Note:
If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the
E1-09 value. The drive will not perform short-circuit braking when b2-01 = E1-09 = 0 Hz.
CLV and CLV/PM (A1-02 = 3, 7)
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at Stop. When
the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04.
Note:
If b2-01 is set to lower than E1-09 (Minimum Frequency), then Zero Speed Control begins at the frequency set to E1-09.
n
b3-01: Speed Search Selection at Start
Determines if Speed Search is automatically performed when a Run command is issued.
No.
b3-01
Setting 0: Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search
is complete.
142
Output
Frequency
Figure 4.19 Short-Circuit Braking at Stop in OLV/PM and AOLV/PM
E1-09 Min. Output Freq.
b2-01 DC Inj. Braking Start Freq.
Output
Frequency
Figure 4.20 Zero Speed Control at Stop in CLV and CLV/PM
Parameter Name
Speed Search Selection at Start
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Short Circuit
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
b2-13
Zero Speed
Control
b2-04
Time
Time
Setting Range
Determined by
0, 1
Default
A1-02