L9: Drive Protection 2 - YASKAWA A1000 Series Quick Start Manual

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
L8-32
Cooling Fan Failure
(04E2)
Selection
L8-35
Installation Method
(04EC)
Selection
L8-38
Carrier Frequency
(04EF)
Reduction
Carrier Frequency
L8-40
Reduction Off Delay
(04F1)
Time
L8-41
High Current Alarm
(04F2)
Selection
L8-55
Internal Braking
(045F)
Transistor Protection
L8-78
Power Unit Output
(02CC)
Phase Loss Protection
L8-93
LSo Detection Time at
(073C)
Low Speed
L8-94
LSo Detection Level at
(073D)
Low Speed
L8-95
Average LSo Frequency
(073F)
at Low Speed
<1> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Default setting is determined by parameter o2-04, Drive Model Selection.
<3> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<4> Default setting is determined by parameter A1-02, Control Method Selection.
u

L9: Drive Protection 2

No.
(Addr.
Name
Hex)
L9-03
Carrier Frequency
(0819)
Reduction Level
<1>
Selection
<1> Available in drive software versions PRG: 1018 and later.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
LCD Display
Determines drive response when a fault occurs with the internal
MC/FAN PS FltSel
cooling fan.
0: Ramp to Stop
0: Ramp to stop
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast stop (Decel to stop using the decel time set in C1-09)
3: Alarm Only
3: Alarm only ("FAn" will flash)
4: Run@L8-19 Rate
4: Continue operation at reduced speed as set in L8-19.
Installation Sel
0: IP00/Open-Chassis enclosure
0: IP00/OpenChassis
1: Side-by-Side mounting
1: Side-by-Side
2: IP20/NEMA 1, UL Type 1 enclosure
2: IP20/Nema Type 1
3: Finless model drive or external heatsink installation
3: Finless/Fin Ext
Fc Reduct dur OL
0: Disabled
0: Disabled
1: Enabled below 6 Hz
1: Active below 6Hz
2: Enabled for the entire speed range
2: Active @ any Spd
Sets the time that the drive continues running with reduced
carrier frequency after the carrier reduction condition is gone.
Fc Reduct Time
Setting 0.00 s disables the carrier frequency reduction time.
High Cur Alm Sel
0: Disabled
0: Disabled
1: Enabled. An alarm is triggered at output currents above
1: Enabled
150% of drive rated current.
0: Disabled. Disable when using a regen converter or optional
braking unit.
DB Tr protection
1: Protection enabled.
0: Disable
1: Enable
Note:
Enables motor protection in the event of output phase loss.
0: Disabled
LF3 Det Sel
1: Enabled
0: Disabled
1: Enabled
Note:
Sets the amount of time until baseblock is executed after
LSO Det Time
detecting pull-out at low speed.
LSO Det Level
Determines the detection level of pull-out at low speed.
Sets the average number of times pull-out can occur at low
Num of LSO Avg
speed.
LCD Display
Selects the level to start frequency reduction or to clear the current
frequency level for automatic carrier frequency reduction.
There is normally no need to change this parameter from the default
value.
0: Reduces the carrier frequency based on the drive rated current that
Fc ReductLvl Sel
is not derated.
0: Disabled
1: Reduces the carrier frequency based on the drive rated current that
1: Enabled
is derated by the carrier frequency and the temperature selected for
C6-02.
Note:
Description
This parameter is not available in models
4A0930 and 4A1200.
This parameter is only available in models
4A0930 and 4A1200.
Description
This parameter is not available in models 4A0930 and
4A1200.
B.8 L: Protection Function
Values
Page
Default: 1
Range: 0 to 4
<2>
Default:
Range: 0 to 3
<3>
Default:
Range: 0 to 2
<4>
Default:
Min.: 0.00 s
Max.: 2.00 s
Default: 0
Range: 0, 1
Default: 1
Range: 0, 1
Default: 1
Range: 0, 1
Default: 1.0 s
Min.: 0.0
Max.: 10.0
Default: 3%
Min.: 0
Max.: 10
Default: 10 times
Min.: 1
Max.: 50
Values
Page
Default: 0
Range: 0, 1
B
307