B.7 H Parameters: Multi-Function Terminals
H1-oo Setting
Function
20 to 2F
External fault
30
PID integral reset
31
PID integral hold
Multi-Step Speed
32
Reference 4
34
PID soft starter cancel PID SFS Cancel
PID input level
35
selection
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
47
Node setup
DC Injection Braking
60
command
External Speed Search
61
command 1
290
H1 Multi-Function Digital Input Selections
LCD Display
20: NO/Always Det,
20: N.O., Always detected, ramp to stop
Ramp to Stop
21: N.C., Always detected, ramp to stop
21: NC/Always Det,
22: N.O., During run, ramp to stop
Ramp to Stop
23: N.C., During run, ramp to stop
22: NO/During
24: N.O., Always detected, coast to stop
RUN, Ramp to Stop
25: N.C., Always detected, coast to stop
23: NC/During
26: N.O., During run, coast to stop
RUN, ramp to stop
27: N.C., During run, coast to stop
24: NO/ Always Det,
28: N.O., Always detected, Fast Stop
Coast to Stop
29: N.C., Always detected, Fast Stop
25: NC/Always Det,
2A: N.O., During run, Fast Stop
Coast to Stop
2B: N.C., During run, Fast Stop
26: NO/During
2C: N.O., Always detected, alarm only (continue running)
RUN, Coast to Stop
2D: N.C., Always detected, alarm only (continue running)
27: NC/During
2E: N.O., During run, alarm only (continue running)
RUN, Coast to Stop
2F: N.C., During run, alarm only (continue running)
28: NO/Always Det,
Fast-Stop
29: NC/Always Det,
Fast-Stop
2A: NO/During
RUN, Fast-Stop
2B: NC/During
RUN, Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During
RUN, Alarm Only
2F: NC/During
RUN, Alarm Only
PID Intgrl Reset
Closed: Resets the PID control integral value.
Open: Performs integral operation.
PID Intgrl Hold
Closed: Maintains the current PID control integral value.
Used in combination with input terminals set to Multi-Step Speed
Multi-Step Ref 4
Reference 1, 2, and 3. Use parameters d1-09 to d1-16 to set reference
values.
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
PID Input Invert
Closed: Inverts the PID input signal.
Open: Stop
Closed: Forward run
FwdRun 2Wire Seq
Note:
Open: Stop
Closed: Reverse run
RevRun 2WireSeq
Note:
Open: Stop
Closed: Run
Run/Stp 2WireSeq
Note:
Open: Forward
Closed: Reverse
FWD/REV
2WireSeq
Note:
Offset Freq 1
Closed: Adds d7-01 to the frequency reference.
Offset Freq 2
Closed: Adds d7-02 to the frequency reference.
Offset Freq 3
Closed: Adds d7-03 to the frequency reference.
CanOpenNID Setup Closed: Node setup for SI-S3 enabled.
DCInj Activate
Closed: Triggers DC Injection Braking.
Closed: Activates Current Detection Speed Search from the maximum
Speed Search 1
output frequency (E1-04).
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 40 or 41.
Determines motor direction, but does not issue a Run
command. Cannot be set together with settings 40 or 41.