YASKAWA A1000 Series Quick Start Manual page 161

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

n
L3-03: Stall Prevention Limit during Acceleration
The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the
lower limit for this reduction as a percentage of the drive rated current.
No.
L3-03
Stall Prevention level during Acceleration
n
L3-04: Stall Prevention Selection during Deceleration
Stall Prevention during deceleration controls the deceleration based on the DC bus voltage and prevents an overvoltage fault
caused by high inertia or rapid deceleration.
No.
L3-04
Stall Prevention Selection During Deceleration
<1> Settings 3 through 5 are not available in OLV/PM. Settings 2 through 5 are not available in AOLV/PM and CLV/PM.
Setting 3 is not available in models 4A0930 or 4A1200.
Setting 0: Disabled
The drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage fault
may occur. If an overvoltage fault occurs, use dynamic braking options or switch to another L3-04 selection.
Setting 1: General-purpose Stall Prevention
The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the DC bus voltage exceeds
the Stall Prevention level and then continues deceleration when the DC bus voltage drops below that level. Stall Prevention
may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input
voltage setting E1-01.
Drive Input Voltage
200 V Class
400 V Class
600 V Class
Note:
1. Do not use this setting in combination with a Dynamic Braking Resistor or other dynamic braking options. If Stall Prevention during
deceleration is enabled, it will be triggered before the braking resistor option can operate.
2. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider
using a dynamic braking option.
Figure 4.36
illustrates the function of Stall Prevention during deceleration.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Name
Stall Prevention Limit during Acceleration
E1-06
Base frequency
Figure 4.35 Stall Prevention Level and Limit During Acceleration
Name
4.6 Basic Drive Setup Adjustments
Setting Range
L3-02
L3-03
Output frequency
Setting Range
Stall Prevention Level during Deceleration
377 Vdc
754 Vdc
1084 Vdc
Default
0 to 100%
50%
Default
<1>
0 to 5
1
4
161

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents