B.7 F: Option Settings

B.7 F: Option Settings
F parameters program the drive to function with option cards.
u
F4: Analog Monitor Card Settings (AO-A3)
No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor
(0391)
Selection
F4-02
Terminal V1 Monitor
(0392)
Gain
F4-03
Terminal V2 Monitor
(0393)
Selection
F4-04
Terminal V2 Monitor
(0394)
Gain
F4-05
Terminal V1 Monitor
(0395)
Bias
F4-06
Terminal V2 Monitor
(0396)
Bias
F4-07
Terminal V1 Signal
(0397)
Level
F4-08
Terminal V2 Signal
(0398)
Level
<1> Set to 000 or 031 when using the terminal in the through mode. This setting can adjust the V1 and V2 terminal output from PLC via MEMOBUS/
Modbus communications or communications option.
u
F5: Digital Output Card Settings (DO-A3)
No.
(Addr.
Name
Hex)
F5-01
Terminal P1-PC Output
(0399)
Selection
F5-02
Terminal P2-PC Output
(039A)
Selection
F5-03
Terminal P3-PC Output
(039B)
Selection
F5-04
Terminal P4-PC Output
(039C)
Selection
F5-05
Terminal P5-PC Output
(039D)
Selection
F5-06
Terminal P6-PC Output
(039E)
Selection
F5-07
Terminal M1-M2
(039F)
Output Selection
F5-08
Terminal M3-M4
(03A0)
Output Selection
294
LCD Display
Sets the monitor signal for output from terminal V1. Set this
parameter to the last three digits of the desired Uo-oo
AO Ch1 Select
monitor. Some U parameters are available only in certain
control modes.
Sets the gain for voltage output via terminal V1.
AO Ch1 Gain
Sets the monitor signal for output from terminal V2. Set this
parameter to the last three digits of the desired Uo-oo
AO Ch2 Select
monitor. Some U parameters are available only in certain
control modes.
Sets the gain for voltage output via terminal V2.
AO Ch2 Gain
Sets the amount of bias added to the voltage output via terminal
V1.
AO Ch1 Bias
Sets the amount of bias added to the voltage output via terminal
V2.
AO Ch2 Bias
AO Opt Level Ch1
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
AO Opt Level Ch2
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
LCD Display
Sets the function for contact output terminals M1-M2, M3-M4,
DO Ch1 Select
and photocoupler output terminals P1 through P6.
DO Ch2 Select
DO Ch3 Select
DO Ch4 Select
DO Ch5 Select
DO Ch6 Select
DO Ch7 Select
DO Ch8 Select
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
Description
Description
Values
Page
Default: 102
Range: 000 to 999
<1>
Default: 100.0%
Min.: -999.9
Max.: 999.9
Default: 103
Range: 000 to 999
<1>
Default: 50.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Values
Page
Default: 0
Range: 0 to 192
Default: 1
Range: 0 to 192
Default: 2
Range: 0 to 192
Default: 4
Range: 0 to 192
Default: 6
Range: 0 to 192
Default: 37
Range: 0 to 192
Default: F
Range: 0 to 192
Default: F
Range: 0 to 192