1.6

F: Option Settings

u

F2: Analog Input Card Settings

These parameters set the drive for operation with the analog input option card AI-A3. If no AI-A3 card is connected, drive
terminals A1 to A3 are enabled regardless of the F2-01 setting. This section describes parameters that govern operation with
an input option card. Refer to the option card instruction manual for specific details on installation, wiring, input signal level
selection, and parameter setup.
n
F2-01: Analog Input Option Card Operation Selection
Determines how the input terminals on the AI-A3 option card are used.
No.
F2-01
Analog Input Option Card Operation Selection
Setting 0: Separate functions for each terminal (V1, V2, V3 replace terminals A1, A2, A3)
Use the H3-oo parameters described in
and gain and bias levels for an analog reference supplied by AI-A3.
Note:
Setting option card terminals for separate input functions (F2-01 = 0) while b1-01 = 3 will trigger an oPE05 error.
Setting 1: Combine input terminal values to create frequency reference (V1, V2, V3 are combined)
This setting adds all three input signals on the AI-A3 option card to create the frequency reference. Set b1-01 to 3 when the
option card is the source of the frequency reference for the drive. Set the gain and bias settings for the frequency reference
supplied from AI-A3 with F2-02 and F2-03.
n
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the combined
input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
F2-02
F2-03
Note:
Enabled only when F2-01 = 1.
u

F3: Digital Input Card Settings

These parameters set the drive for operation with the option card DI-A3. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F3-01: Digital Input Option Card Input Selection
Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
No.
F3-01
Note:
BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Parameter Name
H3-03, H3-04: Terminal A1 Gain and Bias Settings
Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias
Parameter Name
Digital Input Option Card Input Selection

1.6 F: Option Settings

Setting Range
0, 1
on page
98
to set the functions
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0 to 7
Default
0
Default
100.0%
0.0%
Default
0
1