U2: Fault Trace - YASKAWA A1000 Series Quick Start Manual

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

B.13 U: Monitors
No.
(Addr.
Name
Hex)
U1-25
Software Number
(004D)
(Flash)
U1-26
(005B) Software No. (ROM)
U1-27
Message ID (OPR)
(07A8)
U1-28
(07A9) Message ID (INV)
U1-29
Software No. (PWM)
(07AA)
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<2> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using
MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition "192 (maximum value) = drive rated current (A)"
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> In V/f and V/f w/PG control modes, 10 V = drive capacity (kW). In OLV, CLV, OLV/PM, AOLV/PM, and CLV/PM control modes, 10 V = motor
rated power (E2-11) (kW).
u

U2: Fault Trace

No.
(Addr.
Name
Hex)
U2-01
Current Fault
(0080)
U2-02
Previous Fault
(0081)
U2-03
Frequency Reference at
(0082)
Previous Fault
U2-04
Output Frequency at
(0083)
Previous Fault
U2-05
Output Current at
(0084)
Previous Fault
U2-06
Motor Speed at Previous
(0085)
Fault
U2-07
Output Voltage at
(0086)
Previous Fault
U2-08
DC Bus Voltage at
(0087)
Previous Fault
U2-09
Output Power at
(0088)
Previous Fault
U2-10
Torque Reference at
(0089)
Previous Fault
U2-11
Input Terminal Status at
(008A)
Previous Fault
U2-12
Output Terminal Status
(008B)
at Previous Fault
U2-13
Drive Operation Status
(008C)
at Previous Fault
U2-14
Cumulative Operation
(008D)
Time at Previous Fault
322
FLASH ID
CPU 1 SW Number
ROM ID
CPU 2 SW Number
MessageID (OPR)
OPR ID
MessageID (INV)
INV ID
PWM ID
CPU 3 SW Number
Note:
LCD Display
Displays the current fault.
Current Fault
Displays the previous fault.
Last Fault
Displays the frequency reference at the previous fault.
Frequency Ref
Displays the output frequency at the previous fault.
Output Freq
Displays the output current at the previous fault.
Output Current
Note:
Displays the motor speed at the previous fault.
Motor Speed
Displays the output voltage at the previous fault.
Output Voltage
Displays the DC bus voltage at the previous fault.
DC Bus Voltage
Displays the output power at the previous fault.
Output kWatts
Displays the torque reference at the previous fault.
Torque Reference
Displays the input terminal status at the previous fault.
Input Term Sts
Displayed as in U1-10.
Displays the output status at the previous fault. Displayed as in
Output Term Sts
U1-11.
Displays the operation status of the drive at the previous fault.
Inverter Status
Displayed as in U1-12.
Displays the cumulative operation time at the previous fault.
Elapsed time
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
This monitor is only displayed in models
4A0930 and 4A1200.
Description
The unit is expressed in 1 A for models 4A0930
and 4A1200.
Analog
Unit
Output Level
No signal
output available
No signal
output available
No signal
output available
No signal
output available
No signal
output available
Analog
Unit
Output Level
No signal
output available
No signal
output available
No signal
0.01 Hz
output available
No signal
0.01 Hz
output available
No signal
<1> <2>
output available
No signal
0.01 Hz
output available
No signal
0.1 Vac
output available
No signal
1 Vdc
output available
No signal
0.1 kW
output available
No signal
0.1%
output available
No signal
output available
No signal
output available
No signal
output available
No signal
1 h
output available

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents