B.5 E: Motor Parameters
No.
(Addr.
Name
Hex)
E1-04
Maximum Output
(0303)
Frequency
E1-05
Maximum Voltage
(0304)
E1-06
Base Frequency
(0305)
E1-07
Middle Output
(0306)
Frequency
E1-08
Middle Output
(0307)
Frequency Voltage
E1-09
Minimum Output
(0308)
Frequency
E1-10
Minimum Output
(0309)
Frequency Voltage
E1-11
Middle Output
(030A)
Frequency 2
<7>
E1-12
Middle Output
(030B)
Frequency Voltage 2
<7>
E1-13
(030C)
Base Voltage
<6>
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<4> Default setting is determined by parameter E5-01, Motor Code Selection.
<5> In OLV/PM, setting range varies according to the motor code entered to E5-01. The setting range is 0.0 to 400.0 Hz when E5-01 is set to FFFF.
<6> When E1-13, Base Voltage, is set to 0.0, output voltage is controlled with E1-05, Maximum Voltage, = E1-13. When Auto-Tuning is performed,
E1-05 and E1-13 are automatically set to the same value.
<7> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
272
LCD Display
Parameters E1-04 and E1-06 to E1-13 can only be changed
when E1-03 is set to F.
Max Frequency
To set linear V/f characteristics, set the same values for E1-07
and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure
that the five frequencies are set according to the following rules
Max Voltage
to prevent triggering an oPE10 fault:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Setting E1-11 to 0 disables both E1-11 and E1-12 and the above
conditions do not apply.
Base Frequency
Output Voltage (V)
Mid Frequency A
Mid Voltage A
Min Frequency
Min Voltage
Note:
• E1-07, E1-08, and E1-10 are available only in the following
control modes: V/f Control, V/f with PG, Open Loop Vector.
Mid Frequency B
• E1-11, E1-12, and E1-13 are available only in the following
control modes: V/f Control, V/f with PG, Open Loop Vector,
Closed Loop Vector.
Mid Voltage B
Base Voltage
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Some parameters may not be available
depending on the control mode.
Values
Page
<3> <4>
Default:
Min.: 40.0
151
<5>
Max.: 400.0
<3> <4>
Default:
Min.: 0.0 V
151
Max.: 255.0 V
<1>
<3> <4>
Default:
Min.: 0.0
151
<5>
Max.: E1-04
<3>
Default:
151
Min.: 0.0
Max.: E1-04
<3>
Default:
Min.: 0.0 V
151
Max.: 255.0 V
<1>
<3> <4>
Default:
Min.: 0.0
151
<5>
Max.: E1-04
<3>
Default:
Min.: 0.0 V
151
Max.: 255.0 V
<1>
Default: 0.0 Hz
Min.: 0.0
151
Max.: E1-04
Default: 0.0 V
Min.: 0.0
151
Max.: 255.0 V
<1>
Default: 0.0 V
<6>
Min.: 0.0
151
Max.: 255.0 V
<1>