B.8 L: Protection Function
u

L5: Fault Restart

No.
(Addr.
Name
Hex)
L5-01
Number of Auto Restart
(049E)
Attempts
Auto Restart Fault
L5-02
Output Operation
(049F)
Selection
L5-04
Fault Reset Interval
(046C)
Time
L5-05
Fault Reset Operation
(0467)
Selection
u

L6: Torque Detection

No.
(Addr.
Name
Hex)
Torque Detection
L6-01
Selection 1
(04A1)
L6-02
Torque Detection
(04A2)
Level 1
L6-03
Torque Detection
(04A3)
Time 1
Torque Detection
L6-04
Selection 2
(04A4)
L6-05
Torque Detection
(04A5)
Level 2
304
LCD Display
Sets the number of times the drive may attempt to restart after
Num of Restarts
the following faults occur: GF, LF, oC, oH1, ov, PF, rH, rr,
oL1, oL2, oL3, oL4, STo, Uv1.
Restart Sel
0: Fault output not active.
0: Flt Outp Disabld
1: Fault output active during restart attempt.
1: Flt Outp Enabled
Sets the amount of time to wait between performing fault
Flt Reset Wait T
restarts.
0: Continuously attempt to restart while incrementing restart
Fault Reset Sel
counter only at a successful restart (same as F7 and G7).
0: Continuous
1: Attempt to restart with the interval time set in L5-04 and
1: Use L5-04 Time
increment the restart counter with each attempt (same as V7).
LCD Display
0: Disabled
1: oL3 detection only active during speed agree, operation
continues after detection
2: oL3 detection always active during run, operation continues
Torq Det 1 Sel
after detection
0: Disabled
3: oL3 detection only active during speed agree, output shuts
1: OL Alm at SpdAgr
down on an oL3 fault
2: OL Alm dur RUN
4: oL3 detection always active during run, output shuts down
3: OL Flt at SpdAgr
on an oL3 fault
4: OL Flt dur RUN
5: UL3 detection only active during speed agree, operation
5: UL Alm at SpdAgr
continues after detection
6: UL Alm dur RUN
6: UL3 detection always active during run, operation continues
7: UL Flt at SpdAgr
after detection
8: UL Flt dur RUN
7: UL3 detection only active during speed agree, output shuts
down on a UL3 fault
8: UL3 detection always active during run, output shuts down
on a UL3 fault
Sets the overtorque and undertorque detection level.
Torq Det 1 Lvl
Sets the time an overtorque or undertorque condition must exist
Torq Det 1 Time
to trigger torque detection 1.
0: Disabled
1: oL4 detection only active during speed agree, operation
continues after detection
2: oL4 detection always active during run, operation continues
Torq Det 2 Sel
after detection
0: Disabled
3: oL4 detection only active during speed agree, output shuts
1: OL Alm at SpdAgr
down on an oL4 fault
2: OL Alm dur RUN
4: oL4 detection always active during run, output shuts down
3: OL Flt at SpdAgr
on an oL4 fault
4: OL Flt dur RUN
5: UL4 detection only active during speed agree, operation
5: UL Alm at SpdAgr
continues after detection
6: UL Alm dur RUN
6: UL4 detection always active during run, operation continues
7: UL Flt at SpdAgr
after detection
8: UL Flt dur RUN
7: UL4 detection only active during speed agree, output shuts
down on a UL4 fault
8: UL4 detection always active during run, output shuts down
on a UL4 fault
Sets the overtorque and undertorque detection level.
Torq Det 2 Lvl
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
Values
Page
Default: 0
Min.: 0
Max.: 10
Default: 0
Range: 0, 1
Default: 10.0 s
Min.: 0.5
Max.: 600.0
Default: 0
Range: 0, 1
Values
Page
Default: 0
Range: 0 to 8
Default: 150%
Min.: 0
Max.: 300
Default: 0.1 s
Min.: 0.0
Max.: 10.0
Default: 0
Range: 0 to 8
Default: 150%
Min.: 0
Max.: 300