• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and motor
output power cables.
PG-X3 Interface Circuit
PG-X3 Terminal Functions
Terminal Block
TB1
TB2
<1> A separate UL Listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.
PG Encoder Power Supply Voltage
For the PG-X3 option, set the voltage for the PG encoder power supply using jumper CN3 located on the option. Position the
jumper as shown in
Table 7.8
NOTICE: The positioning of jumper CN3 selects the PG encoder power supply voltage (5.5 V or 12 V). Select the voltage level for the PG
encoder connected to the option and motor. If the wrong voltage is selected, the PG encoder may not operate properly or may become
damaged as a result.
Table 7.8 Setting the PG Encoder Power Supply Voltage (IP) with Jumper CN3
Voltage Level
Jumper CN3
PG-X3 Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in
wire ends. Refer to the option manuals for the wire size and torque specifications of other options.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
PG X3
26LS32 level
26LS31 level
Figure 7.12 PG-X3 Interface Circuit
Table 7.7 PG-X3 Option Terminal Functions
Terminal
A+
A–
B+
B–
TB1
Z+
Z–
SD
FE
IP
IG
PG encoder power supply common
SG
a+
TB2
a–
A pulse inverse monitor signal
b+
b–
B pulse inverse monitor signal
z+
z–
Z pulse inverse monitor signal
to select the voltage level.
5.5 V ± 5% (default)
Table
PG Encoder
A+,B+,Z+
A,B,Z
600
A ,B ,Z
A,B,Z 26LS31 level
a+,b+,z+
a ,b ,z
Monitor Signals
SG
Function
A pulse signal input
A inverse pulse signal input
B pulse signal input
B inverse pulse signal input
Z pulse signal input
Z inverse pulse signal input
NC pin (open)
Ground
PG encoder power supply
Monitor signal common
A pulse monitor signal
B pulse monitor signal
Z pulse monitor signal
5.5 V 12 V
CN3
7.9. For simpler and more reliable wiring, use crimp ferrules on the
7.1 Option Card Installation
Description
• Inputs for the A channel, B channel, and Z
pulses from the PG encoder
• Signal level matches RS-422
Open connection port for use when cable
shields should not be grounded
Used as the shield ground termination point.
• Output voltage: 12.0 V ± 5% or 5.5 V ±
5%
• Max. output current: 200 mA
• Output signal for monitoring A channel, B
channel, and Z pulses from the PG encoder
• Signal level matches RS-422
12.0 V ± 5%
5.5 V 12 V
CN3
<1>
7
229