C.2 UL and CSA Standards
<4> Class L fuse is also approved for this rating.
Wiring Fuses for Models 4A0930 and 4A1200
NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage
current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from
Voltage
Model
Class
Input Voltage
4A0930
4A0930 with
12-pulse
Three-
rectification
Phase
400 V
4A1200
Class
4A1200 with
12-pulse
rectification
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL Listed Class 2 power supply source or equivalent only.
Input / Output
Open Collector Outputs
Digital inputs
Analog inputs / outputs
n
Drive Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by Bussmann
Type FWH or FWP fuses as specified in
u

CSA Standards Compliance

n
CSA for Industrial Control Equipment
The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.
u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor
overload protection is UL Listed and in accordance with the NEC and CEC.
348
Table
3.2.
Table C.9 Input Fuses for Models 4A0930 and 4A1200
Selection
Current
480 V
1500 A
480 V
1500 A
Table C.10 Control Circuit Terminal Power Supply
Terminal Signal
P1, P2, PC, DM+, DM-
S1 to S8, SC, HC, H1, H2
+V, -V, A1, A2, A3, AC, AM, FM
Factory Recommended Branch Circuit Protection
Pre-arc
Model
2
2
I
t (A
s)
CS5F-1200
140000 to
FWH-1200A
3100000
FWH-1000A
CS5F-1500
320000 to
FWH-1600A
3100000
FWH-1200A
Requires class 2 power supply
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Figure C.8 CSA Mark
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Input Fuse (Example)
Manufacturer
Rating
Fuji Electric
AC500 V, 1200 A
Bussman
AC500 V, 1200 A
Bussman
AC500 V, 1000 A
Fuji Electric
AC500 V, 1500 A
Bussman
AC500 V, 1600 A
Bussman
AC500 V, 1200 A
Power Supply Specifications
on page 330.
Pre-arc
2
2
I
t (A
s)
276000
351000