No.
(Addr.
Name
Hex)
High Frequency
n3-14
Injection during
(0532)
Overexcitation
Deceleration
n3-21
High-Slip Suppression
(0579)
Current Level
n3-23
Overexcitation
(057B)
Operation Selection
<1> The upper limit of the setting range and default setting are determined by parameters C6-01, Drive Duty Selection, and L8-38, Frequency Reduction
Selection.
u

n5: Feed Forward Control

No.
(Addr.
Name
Hex)
n5-01
Feed Forward Control
(05B0)
Selection
n5-02
Motor Acceleration
(05B1)
Time
n5-03
Feed Forward Control
(05B2)
Gain
<1> Default setting is determined by parameter E5-01, Motor Code Selection.
<2> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
u

n6: Online Tuning

No.
(Addr.
Name
Hex)
n6-01
Online Tuning
(0570)
Selection
n6-05
Online Tuning Gain
(05C7)
u

n8: PM Motor Control Tuning

No.
(Addr.
Name
Hex)
n8-01
Initial Rotor Position
(0540)
Estimation Current
n8-02
Pole Attraction Current Pull-In Current
(0541)
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
LCD Display
0: Disabled
HarmInj@HiFlxBrk
1: Enabled
0: Disabled
1: Enabled
Sets output current level at which the drive will start reducing
the overexcitation gain in order to prevent a too high motor slip
Hflux I Supp Lvl
during Overexcitation Deceleration. Set as a percentage of the
drive rated current.
Hflux Brake Sel
0: Enabled in both directions
0: Enabled-Both Dir
1: Enabled only when rotating forward
1: Enabled-Fwd only
2: Enabled only when in reverse
2: Enabled-Rev only
LCD Display
Feedfoward Sel
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the time required to accelerate the motor at the rated torque
from stop to rated speed.
Motor Accel Time
Sets the ratio between motor and load inertia. Lower this setting
Feedfoward Gain
if overshoot occurs at the end of acceleration.
LCD Display
0: Disabled
1: Line-to-line resistance tuning
Online Tune Sel
2: Voltage correction. Setting not possible when Energy Saving
is enabled (b8-01).
Decrease this setting for motors with a relatively large rotor
R1 Comp Gain
time constant.
LCD Display
Sets the current used for initial rotor position estimation as a
InitRotPosDetCur
percentage of the motor rated current (E5-03). If the motor
nameplate lists an "Si" value, that value should be entered here.
Sets the current during initial polar attraction as a percentage
of the motor rated current.
Note:
Description
Description
Description
Description
This parameter is not available in models
4A0930 and 4A1200 for CLV/PM.
B.9 n: Special Adjustment
Values
Page
Default: 0
Range: 0, 1
Default: 100%
Min.: 0
Max.: 150
Default: 0
Range: 0 to 2
Values
Page
Default: 0
Range: 0, 1
<1> <2>
Default:
Min.: 0.001 s
Max.: 10.000 s
Default: 1.00
Min.: 0.00
Max.: 100.00
Values
Page
Default: 0
Range: 0 to 2
Default: 1.0
Min.: 0.1
Max.: 50.0
Values
Page
Default: 50%
Min.: 0
Max.: 100
Default: 80%
Min.: 0
Max.: 150