7.1 Option Card Installation
Note:
1. The option package includes two ground wires. Use the longer wire when plugging the option into connector CN5-C on the
drive side. Use the shorter wire when plugging the option into connector CN5-B. Refer to the Option Installation manual for
more information.
2. There are two screw holes on the drive for use as ground terminals (H). When connecting three options, two ground wires
will need to share the same drive ground terminal.
4.
Prepare and connect the wire ends as shown in
Torques of PG-X3 Option on page 230
page 230
to confirm that the proper tightening torque is applied to each terminal. Take particular precaution to ensure
that each wire is properly connected and that wire insulation is not accidentally pinched into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections
could result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified
tightening torque may result in erroneous operation, damage to the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not contact other wiring.
Insufficient insulation may cause a short circuit and damage the option or drive.
5.
Wire the motor PG encoder to the terminal block on the option. Refer to
instructions.
Refer to PG-B3 Option Terminal Functions on page 226
224
H
G
Figure 7.4 Connect the Ground Wire
or
Refer to Wire Gauges and Tightening Torques of PG-X3 Option on
Shield
PG option terminal
Figure 7.5 Preparing Ends of Shielded Cable
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
about 5.5 mm (7/32")
When not using
crimped insulated
sleeves
Figure 7.6 Preparing and Connecting Cable Wiring
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
M
F
Figure 7.5
and
Figure
7.6.
Insulation
PG at motor
Ground Terminal
Shield sheath
FE/SD
(Insulate with electrical tape
or shrink tubing)
Screwdriver blade size
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Loosen the screws and
insert the wire into the
opening on the terminal block.
To PG at motor
(do not solder ends)
Figure 7.7
for a detailed description of the option terminal functions.
Refer to Wire Gauges and Tightening
Option terminal block
and
Figure 7.11
for wiring