YASKAWA A1000 Series Quick Start Manual page 165

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

Input Value
Parameter
Control Mode
Motor rated power
Motor rated voltage
Motor rated current
Motor rated frequency
Number of motor poles
Motor rated Speed
PG Number of pulses per
revolution
Motor no-load current
Motor rated Slip
Motor iron loss
<1> Input data is needed for CLV/PM only.
<2> Motor no-load current is required. If the no-load current is not shown on the motor nameplate, use the default value. The default value is set for
Yaskawa standard motors.
n
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1-oo and E5-oo when a PM motor is used. Additionally, the
feature also sets some F1-oo parameters for speed feedback detection in Closed Loop Vector.
Type
Setting
PM Motor Parameter
T2-01 = 0
Settings
PM Stationary Auto-
T2-01 = 1
Tuning
PM Stationary Auto-
Tuning for Stator
T2-01 = 2
Resistance
Z Pulse Offset Tuning
T2-01 = 3
Back EMF Constant
T2-01 = 11
Tuning
High Frequency
Injection Parameter
T2-01 = 13
Tuning
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Table 4.29 Auto-Tuning Input Data
Input
Unit
0
Standard
A1-02
2, 3
T1-02
kW
YES
T1-03
Vac
YES
T1-04
A
YES
T1-05
Hz
YES
T1-06
-
YES
T1-07
r/min
YES
T1-08
-
YES
T1-09
A
T1-10
Hz
T1-11
W
Table 4.30 Types of Auto-Tuning for Permanent Magnet Motors
Application Conditions and Benefits
• Motor does not rotate during Auto-Tuning.
• Motor data similar to
report or motor nameplate.
• A motor test report listing motor data is not available.
• Drive automatically calculates and sets motor parameters.
• Useful to tune the drive when the motor data were set up
manually or by motor code and the cable is longer than 50
m.
• Should also be performed if the cable length has changed
after prior tuning.
• PG encoder has been replaced. Calculates the Z Pulse
offset.
• Requires the motor to rotate with no load or very low load.
• Use when a motor test is not available.
• Tunes the motor induction voltage only.
• Should be performed after motor data are set and the
encoder offset is adjusted.
• The motor must be uncoupled from the mechanical system
(remove loads).
• Perform High Frequency Injection Parameter Tuning after
setting motor parameters.
Permanent Magnet Motors on page 165
• The motor rotated in reverse or STo fault (Motor Step-Out)
occurred at startup in OLV/PM.
• Low speed and insufficient or no torque after activating the
high frequency injection control (n8-57 = 1) in AOLV/
PM.
Note:
High Frequency Injection cannot be used with
an SPM motor.
Tuning Type (T1-01)
2
1
Line-to-Line
Stationary 1
Resistance
2, 3
0, 1, 2, 3
YES
YES
YES
YES
YES
YES
YES
YES
<1>
<1>
YES
<2>
YES
Table 4.31
are available from test
Refer to Auto-Tuning for
for details.
4.7 Auto-Tuning
3
4
Rotational for
Stationary 2
V/f Control
0, 1
2, 3
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
<1>
YES
YES
YES
YES
Control Mode
OLV/PM
AOLV/PM
YES
YES
YES
YES
YES
YES
YES
5
Stationary 3
2, 3
YES
YES
YES
YES
YES
YES
<1>
YES
YES
CLV/PM
YES
YES
YES
YES
YES
4
YES
165