YASKAWA A1000 Series Quick Start Manual page 245

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

Item
Motor Protection
Momentary Overcurrent
Protection
Overload Protection
Overvoltage Protection
Undervoltage Protection
Protection
Functions
Momentary Power Loss
Ride-Thru
Heatsink Overheat
Protection
Braking Resistor Overheat
Protection
Stall Prevention
Ground Protection
DC Bus Charge LED
Area of Use
Ambient Temperature
Humidity
Environment
Storage Temperature
Altitude
Vibration/Shock
Standard
Protection Design
<1> Select control modes in accordance with drive capacity.
<2> High-frequency current superposition (n8-57=1) is available.
<3> Perform Rotational Auto Tuning.
<4> Contact Yaskawa or your nearest sales representative if using a PM motor other than Super Energy-saving Motors manufactured by Yaskawa Motor
Co., Ltd. (SSR1 series and SST4 series with standard specifications).
<5> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<6> Disable Stall Prevention during deceleration (L3-04 = 0) when using a regenerative converter, a regenerative unit, a braking resistor or the Braking
Resistor Unit. The default setting for the Stall Prevention function will interfere with the braking resistor.
<7> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed
down to zero in the shortest time.
<8> Actual specifications may vary depending on motor characteristics.
<9> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<10> May be shorter due to load conditions and motor speed.
<11> A separate Momentary Power Loss Ride-Thru Unit is required for models 2A0004 to 2A0056 and 4A0002 to 4A0031 if the application needs to
continue running for up to 2 seconds during a momentary power loss.
<12> Ground protection is triggered when a ground short circuit occurs while the drive is running. The ground protection cannot be provided when the
impedance of the ground fault path is too low, or when the drive is powered up while a ground fault is present at the output.
<13> Models 4A0930 and 4A1200 are rated at 5.9 m/s
<14> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type 1
protection while maintaining IP20 conformity. This is applicable to models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Electronic thermal overload relay
Drive stops when output current exceeds 200% of Heavy Duty Rating
Drive stops after 60 s at 150% of rated Heavy Duty output current
200 V class: Stops when DC bus voltage exceeds approx. 410 V
400 V class: Stops when DC bus voltage exceeds approx. 820 V
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class: Stops when DC bus voltage falls below approx. 380 V
600 V class: Stops when DC bus voltage falls below approx. 475 V
Immediately stop after 15 ms or longer power loss.
Continuous operation during power loss than 2 s (standard)
Thermistor
Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Stall Prevention is available during acceleration, deceleration, and during run.
<12>
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
IP20/NEMA 1, UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F)
Finless Type: IP20/IP00 enclosure: -10 °C to +45 °C (14 °F to 113 °F)
95 RH% or less (no condensation)
-20 °C to +60 °C (-4 °F to +140 °F) short-term temperature during transportation
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
<13>
2
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
(2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099)
2
2.0 m/s
(2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)
• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1
• Two Safe Disable inputs and one EDM output according to ISO/EN 13849-1 Cat. 3 PLd, IEC/EN
61508 SIL2
• CSA
IP00/Open Type enclosure, IP20/NEMA 1, UL Type 1 enclosure
2
.
A.3 Drive Specifications
Specification
<9>
<10>
<11>
<14>
A
245