Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is
automatically reduced in the constant power range (speed beyond base speed). A setting of 100% is equal to the drive rated
current.
The Stall Prevention level can be adjusted using an analog input.
No.
L3-06
<1> The upper limit and default for this setting is determined by C6-01 and L8-38.
n
L7-01 to L7-04: Torque Limits
These parameters set the torque limits in each quadrant.
No.
L7-01
L7-02
L7-03
L7-04
Note:
If the multi-function analog input is programmed for "10: Forward torque limit", "11: Reverse torque limit", "12: Regenerative torque
limit", or "15: General torque limit", the drive uses the lowest value from L7-01 through L7-04, or analog input torque limit.
REV motor rotation
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Name
Stall Prevention Level During Run
Name
Forward Torque Limit
Reverse Torque Limit
Forward Regenerative Torque Limit
Reverse Regenerative Torque Limit
Positive torque reference
REV run regenerative
10: Positive Torque Limit
12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-04
Quadrant 2
Quadrant 3
11: Negative Torque Limit
15: Torque Limit
Parameter L7-02
REV run motoring
Negative torque reference
Figure 4.37 Torque Limit Parameters and Analog Input Settings
4.6 Basic Drive Setup Adjustments
Setting Range
30 to 150%
Setting Range
FWD run motoring
10: Positive Torque Limit
15: Torque Limit
Parameter L7-01
Quadrant 1
Quadrant 4
11: Negative Torque Limit
12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-03
FWD run regenerative
Default
<1>
Default
0 to 300%
200%
0 to 300%
200%
0 to 300%
200%
0 to 300%
200%
FWD motor rotation
<1>
4
163