C.2 UL and CSA Standards
Wire Gauge (AWG, kcmil)
Drive Model
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
4A0414
3/0 × 4P
4/0 × 4P
4A0515
4A0675
4A0930
4A1200
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in the tables
below.
Table C.7 Factory Recommended Drive Branch Circuit Protection (Normal Duty)
Nominal
Drive Model
Output Power
HP
2A0004
0.75
2A0006
1 - 1.5
2A0008
2A0010
2A0012
2A0018
2A0021
2A0030
344
Screw
Size
4/0 × 2P
M12
250 × 2P
300 × 2P
3/0 × 4P
4/0 × 4P
M12
250 × 4P
300 × 2P
4/0 × 4P
M12
250 × 4P
300 × 4P
3/0 × 8P
4/0 × 8P
M12
250 × 8P
300 × 8P
4/0 × 8P
M12
250 × 8P
300 × 8P
AC Drive Input
Amps
3.9
7.3
2
8.8
3
10.8
3
13.9
5
18.5
7.5
24
10
37
Crimp
Terminal
Model
Machine No.
Number
100-L12
YF-1
YET-300-1
150-L12
80-L12
YF-1
100-L12
YET-300-1
150-L12
100-L12
YF-1
YET-300-1
150-L12
80-L12
YF-1
100-L12
YET-300-1
150-L12
100-L12
YF-1
YET-300-1
150-L12
Normal Duty
MCCB Rating
Time Delay Fuse
Amps
Rating Amps
<1>
200 V Class
15
6.25
15
12
15
15
20
17.5
25
20
35
30
45
40
60
60
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Tool
Insulation
Cap Model
Die Jaw
No.
TD-324,
TP-100
TD-312
TD-325,
TP-150
TD-313
TD-323,
TP-080
TD-312
TD-324,
TP-100
TD-312
TD-325,
TP-150
TD-313
TD-324,
TP-100
TD-312
TD-325,
TP-150
TD-313
TD-323,
TP-080
TD-312
TD-324,
TP-100
TD-312
TD-325,
TP-150
TD-313
TD-324,
TP-100
TD-312
TD-325,
TP-150
TD-313
Non-time Delay
Fuse Rating
<2>
<3>
Amps
10
20
25
30
40
50
70
110
<1>
Code
100-051-560
100-051-562
100-051-558
100-051-560
100-051-562
100-051-560
100-051-562
100-051-558
100-051-560
100-051-562
100-051-560
100-051-562
Bussmann Semi-
conductor Fuse
Rating (Fuse
<4>
Ampere)
FWH-70B (70)
FWH-70B (70)
FWH-70B (70)
FWH-70B (70)
FWH-70B (70)
FWH-90B (90)
FWH-90B (90)
FWH-100B (100)