YASKAWA A1000 Series Quick Start Manual page 332

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

C.1 European Standards
Drive Model
5A0125
5A0145
5A0192
5A0242
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
Figure C.2 Example of DC Power Supply Input (Two Drives Connected in Series)
Note:
1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.
Refer to Standard Connection Diagram on page 80
3. The recommended fuses and fuse holders are made by Fuji Electric.
332
Model
FWP-350A
FWP-350A
FWP-600A
FWP-600A
DC power supply
(converter)
Fuse
+
+1
_
_
Fuse
+1
_
for an AC power supply.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Fuse Type
Manufacturer: Bussmann
Fuse Ampere Rating (A)
U/ T1
V/ T2
M
W/ T3
Drive
U/ T1
M
V/ T2
W/ T3
Drive
350
350
600
600