F: Option Settings; F1: Pg Speed Control Card Settings - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.6 F: Option Settings

2.6
F: Option Settings

◆ F1: PG Speed Control Card Settings

Yaskawa offers a PG-X3 and PG-B3 motor encoder PG option card. Use the CN5-C port when using only one PG option
card and use the CN5-C and CN5-B ports when using two PG option cards. When programming one of the contact input
to act as a switch between two motors (H1-
connected to CN5-B for motor 2.
Table 2.18
lists the parameters that must be set for each option card port.
Port
CN5-C and CN5-B
F1-02 to F1-04, F1-08 to F1-11, F1-14
(common)
CN5-C only
F1-01, F1-05, F1-06, F1-20
CN5-B only
F1-31, F1-32, F1-35, F1-36
F1-01, F1-31: PG 1 and PG 2 Pulses Per Revolution
Sets the number encoder number of pulses per revolution.
No.
F1-01
F1-31
<1> For details on the default settings, refer to
F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time
A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. The stopping method
when PGo occurs should be set to parameter F1-02.
No.
F1-02
Operation Selection at PG Open Circuit (PGo)
F1-14
PG Open-Circuit Detection Time
Parameter F1-02 Settings:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Setting 4: No alarm display
Note: Due to potential damage to motor and machinery, the "Alarm only" and "No alarm display" setting should be used only under
special circumstances.
F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An overspeed error (oS) is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set
in F1-09. The stopping method when an overspeed fault occurs can be selected in parameter F1-03.
No.
F1-03
Operation Selection at Overspeed (oS)
F1-08
F1-09
Overspeed Detection Delay Time
<1> For details on the default settings, refer to
158
= 16), use the card connected to port CN5-C for motor 1 and use the card
Table 2.18 Option Card Ports and Corresponding Parameters
Parameter Name
PG 1 Pulses Per Revolution
PG 2 Pulses Per Revolution
Control Mode Dependent Parameter Default Values on page
Parameter Name
Parameter Name
Overspeed Detection Level
Control Mode Dependent Parameter Default Values on page
Parameters
Option Port
Setting Range
CN5-C
0 to 60000 ppr
CN5-B
0 to 60000 ppr
Option Port
Setting Range
CN5-B, CN5-C
0 to 4
CN5-B, CN5-C
0.0 to 10.0 s
Option Port
Setting Range
CN5-B, CN5-C
0 to 3
CN5-B, CN5-C
0 to 120%
CN5-B, CN5-C
0.0 to 2.0 s
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
Determined by A1-
02
<1>
600 ppr
79.
Default
1
2.0 s
Default
1
115%
Determined by A1-
02
<1>
79.

Advertisement

Table of Contents
loading

Table of Contents